Gunning Heating Products

All Steel Heater Batteries

(Previously Manufactured By MYSON Eng Co Ltd.)


 

 

 

 

Custom built to last

 

Special Features

 

* Suitable for use with steam, high or low pressure hot water.
* All welded construction for reliability
* Designed and built to meet customer's requirements.
* Application industries include Heating and Ventilating, Motor, Food Processing, Chemical and Water Treatment

Gunning steel heater batteries incorporate our own spirally wound gilled tubes, welded into steel headers. Flanged or screwed connections can be supplied to suit customer’s requirements.

Generally, batteries for use with steam have vertical tubes. The top header being firmly suspended from inside of the casing, the bottom headers are located in guides allowing for expansion or contraction within the casing.

Hot water batteries are of similar construction but have horizontal tubes.


Specification


Primary Heating Surface
Gunning all steel heater batteries are constructed from best quality medium or heavy weight steel tube to dimensions and weights in accordance with B.S.1387. Other material specifications can be supplied upon request. All headers and bends will comply to B.S.1387, or other materials to meet the required specification.

Secondary Heating Surface

18g. or 20g. steel tape of varying widths is wound in a continuous spiral onto tubes at varying pitches under
considerable tension, leaving the fin of semi-flat profile and having a regular crimped contact area with the primary tubes resulting in a perfect mechanical bond with excellent heat characteristics.

Connections
Flanged or plain ends for welding are normally supplied and screwed ends can be provided when required.

Casings
Galvanised pressed steel casings, with a channel section; provide a rigid frame supporting the elements and headers. Close spaced drillings are provided for duct connections as standard. Special connection requirements are provided on request.

Vents and Drains
Vents and drains are not normally fitted unless specifically called for at the time of the enquiry or placing the order. Due to the multiplicity of system designs the decision to provide vents and drains must be left to the customer. Every advice is available on this from Gunning engineers.

Operating Mediums

To be specified at the time of the enquiry when material specifications will be determined to meet the required conditions.

Tests
Completed coils are tested hydraulically to 500 p.s.i.g. or 35.153 Kg/cm2 unless otherwise specified.

Finish
All heat transfer surfaces are treated with heat resisting paint as standard, or alternatively, can be zinc coated or galvanised if required. Casings are self colour unless otherwise specified.

Ordering
The following information should be given when requiring a quotation.

* Air quantity in cu. ft./min or m3/s
* Air temperature on coil.
* Air temperature off coil.
* Heating medium.
* Limitations regarding size and hydraulic pressure drop.
* Direction of air flow, i.e., vertical or horizontal
* Working pressure of coil and test pressure
* Internal or external headers to the casings.


Back to Main Menu

 

© Copyright 1999, Gunning Engineering Ltd,
contact Web-Manager@Gunning Heating Products